LF-TP LON

Description

The LON three-point module with 6 digital inputs, 2 two-level relay outputs and 2 digital outputs was developed for decentralized switching tasks. It is suitable for switching, for example, multi-level pumps, fans, burners or similar. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The inputs and outputs are scanned and activated by SNVT network variables. The input terminals 1 to 6 are wired with the C2 terminals on two poles to potential-free switches or contacts. The module has a manual control for the outputs, which is activated only in configured mode. Suitable for decentralized mounting in serial sub-distributor.

  • Connection with screw type terminal blocks
Technical Data
General Data
TP/FT-10, free topology
FT5000
78 KBit/s
24 V AC/DC +/- 10 % (SELV)
220 mA (AC) / 90 mA (DC)
100 %
550 ms
6 x digital contacts
4.5 V DC
2 x two-level
250 V AC
6 A / output
2 NO (DPST-NO) (photoMOS)
40 V AC/DC
100 mA
Green and yellow LED
50 x 69.3 x 60 mm
126 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory
Accessories
Part number
11085913
4250184135814
Downloads
× Do you have any questions?