FDE 4 24 V AC/DC CAN

Description

CAN module with 4 digital inputs, which can be operated as contact or voltage inputs. It is suitable for detecting switch states, for example, of electrical limit switches on vent valves or auxiliary contacts of power contactors. The fieldbus module is an input module for universal use. It is controlled by means of the CAN bus. The module is addressed by means of an adjustable address, and the input states are transmitted in data bytes. If there is one (or more) relay output module(s) with the same address in the system, the respective outputs are switched.

  • Connection with screw type terminal blocks
Technical Data
General Data
CAN
00 to 99
2.0B passive (two-wire bus)
20 to 500 kBit/s
24 V AC/DC +/- 10 % (SELV)
63 mA (AC) / 21 mA (DC)
100 %
550 ms
4 x digital
less than 7 V DC
Green, red and yellow LED
35 x 69.3 x 60 mm
83 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory