TMR-E12 without error memory, 230 V AC, 1 changeover contact

auslaufartikel_en
Description

The thermistor relay is used as protection relay for motors against thermal overload (inadmissible heating). This heating might be caused by mechanical overload on the shaft or when operating the motor with inadmissible voltages. A PTC thermistor is used as sensor. It should be mounted to the part of the motor that heats most in case of overload (e.g. integrated in motor winding). The device can also be used for motors with integrated thermo switch.

  • Variant:
  • 230 V AC
  • 1 changeover contact (SPDT)
916639
928381
928360
870647
Technical Data
General Data
230 V AC
100 ms
12 V
1 mA
1.8 kOhm
3.0 kOhm, +/- 5%
1 (SPDT) changeover contact
250 V
4 A
1 x 107
1 x 105
1200 cycles/h
Green and red LED
22.5 x 75 x 95 mm
150 g
0 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory
Part number
11031505
4250184118688
Downloads