BMT-CI4 BACnet MS/TP

The BACnet MS/TP with 4 analog inputs was developed for decentralized switching tasks. It is suitable for detecting currents and voltages of, for example, active temperature sensors, electrical vent and mixing valves, valve positions, etc. Each input can be set as current or voltage input by DIP switches on the front. The inputs can be scanned with standard objects via a BACnet client. Module address and bit rate are set with the two rotary switches on the front.Suitable for decentralized mounting on TH35 rails according to IEC 60715 in electrical distribution cabinets.

Protocol BACnet MS/TP
Addressing range 00 to F9
Bus interface RS485 (two-wire bus)
Transmission rate 9600 to 115200 bit/s
Operating voltage range 24 V AC/DC ± 10 % (SELV)
Current consumption 25 mA (AC) / 10 mA (DC)
Relative duty cycle 100 %
Inputs 4 x analog
Input / voltage 0 V to 10 V DC
Input / resolution 1 mV (0 to 100 %)
Input / error 10 mV
Input / current 0 (4) to 20 mA DC
Input / resolution 2 µA
Input / error 20 µA
Display Green, red and yellow LED
Dimensions (W x H x D) 35 x 70 x 65 mm
Weight 84 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal blocks IP40 / IP20

Technical Data 

  • P/N1108901332
    Colorgray
    Feature 14x IN (U or I) active
    EAN-No4250184165682