Compact Linux I/O platform with 27 analog/digital inputs/outputs, some of them with manual control. Integrated web interface for developing your own decentralized automation controllers. Applications can be programmed using the Linux Shell installed on the server or using C/C++ and JAVA development environments. The network is connected by means of a standard RJ45 Ethernet interface. External I/O extension with up to 6 optional modules of the EW-xxxx series possible.Suitable for decentralized mounting in serial sub-distributor.

Operating voltage 24 V AC/DC / +/- 10% / 50/60 Hz
Current consumption 450 mA (AC) / 225 mA (DC)
Network Ethernet 10/100MBit, RJ45
Protocol TCP/IP and BACnet/IP
Controller ARM9 180 MHz
Internal memory 64 MB RAM / 64 MB Flash
External memory microSD up to 4 GB
Real time clock Error 1 s/day, 24 h power reserve
Operating system embedded Linux
External I/O interfaces RS485 with MC protocol
Inputs / digital 8x; 4 of them can be used as S0 acc. to DIN EN 62053-31
Inputs / resistance 4x analog 40 Ohm to 4 MOhm
Inputs / voltage 4x analog 0 to 10 V DC
Outputs / relays 3x changeover contacts (3PDT)/250 V AC/5 A
2x changeover contacts (DPDT)/250 V AC/10A
1x two-level / 250 V AC / 5 A
Outputs / triac 2x 20 to 250 V AC / 0.5 A
Outputs / transistor 3x PNP / 24 V DC / 20 mA
1x PNP / 24 V DC / 30 mA
Outputs / voltage 3x analog 0 to 10 V DC
Dimensions (W x H x D) 125 x 93 x 60.81 mm, 7HP, TH35
Weight 430 g
Operation / storage -5° to +55°C / -20° to + 70° C
Ingress protection IP20