Search form

Languages

BMT-TP BACnet MS/TP

The BACnet MS/TP three-point module with 6 digital inputs, 2 two-level relay outputs and 2 digital outputs was developed for decentralized switching tasks. It is suitable for switching, for example, multi-level pumps and fans or louvers. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The inputs and outputs can be switched and scanned by means of standard objects via a BACnet client. The input terminals 1 to 6 are wired with the C2 terminals on two poles to potential-free switches or contacts. The module has a manual control for the outputs. The module address and the baud rate are set by means of two address switches on the front.Suitable for decentralized mounting in serial sub-distributor.

Protocol BACnet MS/TP
Addressing range 00 to F9
Bus interface RS485 (two-wire bus)
Transmission rate 9600 to 115200 baud
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 100 mA (AC) / 40 mA (DC)
Relative duty cycle 100 %
Inputs 6 x digital contacts
Input / switching threshold 4.5 V DC
Outputs (relay) 2 x two-level
Output / switching voltage 250 V AC
Output / current 6 A / output
Outputs (digital) 2 NO (DPST-NO) (photoMOS)
Output / switching voltage 40 V AC/DC
Output / current 100 mA
Display Green, red and yellow LED
Dimensions (W x H x D) 50 x 69.3 x 60 mm
Weight 126 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal blocks IP40 / IP20

Technical Data 

  • P/N11088813
    Colorgray
    Feature 16x IN (contact)
    Feature 22x OUT (relay CO), 2x OUT (opto NO)
    EAN-No4250184158899

Downloads

pdf BACnet software manual PICS (BMT) 2.01 MB
pdf Data sheet 11088813 3.18 MB
pdf Instruction 11088813 1.5 MB
lock 3D data - STEP / IGES
11088813
1.38 MB
last update on Tuesday, 11. July 2017 - 6:54