Search form



The BACnet MS/TP module with 4 digital triac outputs was developed for decentralized switching tasks. It is suitable for switching electrical components, such as relays, contactors, HLK valves, etc. The outputs can be switched by means of standard objects via a BACnet client. In addition, the outputs can be overridden manually by means of switches on the device. The module is addressed and the baud rate is set by means of two address switches on the front.Suitable for decentralized mounting in serial sub-distributor.

Protocol BACnet MS/TP
Addressing range 00 to F9
Bus interface RS485 (two-wire bus)
Transmission rate 9600 to 115200 baud
Operating voltage range 20 V to 28 V AC/DC (SELV)
Current consumption 100 mA (AC) / 40 mA (DC)
Relative duty cycle 100 %
Output / contacts 4 digital outputs (triac)
Output / switching voltage 24 V AC up to max. 250 V AC
Output / continuous current 0.5 A / output
Output / switching current 0.8 A (less than 30 s)
Output / switch-on current 10 A (less than 20 ms)
Display Green, red and yellow LED
Dimensions (W x H x D) 35 x 70 x 75 mm
Weight 95 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N11088013
    Feature 14x OUT (triac)
    Feature 2


pdf BACnet software manual PICS (BMT) 1.2 MB
pdf Data sheet 11088013 281.4 KB
pdf Instruction 11088013 1.02 MB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
last update on Tuesday, 6. September 2016 - 4:30