Search form



Switch-on module for bus connection, supply voltage and adjustable bus termination. The switch-on module was developed as wiring help for supplying the supply voltage and a two-wire bus to the LON bus modules. The supply voltage and the two-wire bus are led to the upper part of the housing over a sturdy terminal block with a cross section of max. 2.5 mm² and connected to the modules by means of the jumper. Using a suitable interface cable, the two-wire bus can be connected to a PC over the two RJ45 jacks. A bus terminating resistor of 52.3 Ohm (R/2) for free network topology and 105 Ohm (R) for line topology can be set by means of the jumper under the removable cover.Suitable for decentralized mounting in serial sub-distributor.

Operating voltage range 20 V to 28 V AC/DC (SELV)
Current consumption less than 5 mA
Switch-on duration relative 100 %
Display Green LED
Dimensions (W x H x D) 35 x 70 x 78 mm
Weight 75 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N11087913
    Feature 1
    Feature 2


pdf Data sheet 11087913 4.53 MB
pdf Instruction 11087913 1.99 MB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
lock LON Resource files 4.29 KB