MR-CI4 Modbus RTU

The Modbus module with 4 analog inputs was developed for decentralized switching tasks. It is suitable for detecting currents and voltages of, for example, active temperature sensors, electrical vent and mixing valves, valve positions, etc. Each input can be set as current or voltage input by DIP switches on the front.The inputs can be scanned with standard registers via a Modbus master. The module address, the baud rate and the parity are set with two rotary switches on the front or by software.Suitable for decentralized mounting on TH35 rails according to IEC 60715 in electrical distribution cabinets.

Protocol Modbus RTU
Address range 00 to 99
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage range 20 V to 28 V AC/DC (SELV)
Current consumption 25 mA (AC) / 10 mA (DC)
Relative duty cycle 100 %
Inputs 4 x analog
Input / voltage 0 V to 10 V DC
Input / resolution 1 mV (0 to 100 %)
Input / error 10 mV
Input / current 0 (4) to 20 mA DC
Input / resolution 2 µA
Input / error 20 µA
Display Green, red LED
Dimensions (W x H x D) 35 x 70 x 65 mm
Weight 95 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal blocks IP40 / IP20

Technical Data 

  • P/N1108401332
    Feature 14x IN (U or I) active
    Feature 2


pdf Data sheet 1108401332 329.13 KB
pdf Instruction 1108401332 1.29 MB
pdf Modbus software manual 698.96 KB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB