Search form

Languages

MR-SI4 Modbus RTU

The Modbus module with 4 S0 inputs to DIN EN 62053-31 class A was developed for decentralized switching tasks. It is suitable for counting S0 counter pulses. This allows very good integration of the module into an energy controlling system. In case of a power failure, the last counter readings are saved. The inputs can be scanned by means of standard registers via a Modbus master. Module address, bit rate and parity are set with two rotary switches on the front or by software.Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Protocol Modbus RTU
Address range 00 to 99
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 170 mA (AC) / 65 mA (DC)
Relative duty cycle 100 %
Inputs 4 x S0 input, class A
Input / acc. to standard DIN EN 62053-31
Display Green, red and yellow LED
Dimensions (W x H x D) 35 x 69.3 x 60 mm
Weight 83 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal blocks IP40 / IP20

Technical Data 

  • P/N11083913
    Colorgray
    Feature 14x IN (S0 impulse)
    EAN-No4250184161035

Downloads

pdf Data sheet 11083913 3.14 MB
pdf Instruction 11083913 1.47 MB
pdf Modbus software manual 1.35 MB
pdf Produktuebersicht C|Logline 899905-05 EN 5.07 MB
lock 3D data - STEP / IGES
11083913
740.15 KB
zip Modbus Configuration Tool V1.20 752.7 KB
last update on Thursday, 25. May 2017 - 3:53