Search form

Languages

MR-TP Modbus RTU

The Modbus three-point module with 6 digital inputs, 2 two-level relay outputs and 2 digital outputs was developed for decentralized switching tasks. It is suitable for switching, for example, multi-level pumps and fans or louvers. With strong inductive loads, we recommend protecting the relay contacts additionally with an RC element. The inputs and outputs can be switched and scanned by means of standard registers via a Modbus master. The input terminals 1 to 6 are wired with the C2 terminals on two poles to potential-free switches or contacts. The module has a manual control for the outputs. Module address, bit rate and parity are set with two rotary switches on the front or by software.Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Protocol Modbus RTU
Address range 00 to 99
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 100 mA (AC) / 40 mA (DC)
Relative duty cycle 100 %
Inputs 6 x digital contacts
Input / switching threshold 4.5 V DC
Outputs (relay) 2 x two-level
Output / switching voltage 250 V AC
Output / current 6 A / output
Outputs (digital) 2 NO contacts (DPST-NO) (photoMOS)
Output / switching voltage 40 V AC/DC
Output / current 100 mA
Display Green, red and yellow LED
Dimensions (W x H x D) 50 x 70 x 75 mm
Weight 126 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N11083813
    Colorgray
    Feature 16x IN (contact)
    Feature 22x OUT (relay CO), 2x OUT (opto NO)
    EAN-No4250184161004

Downloads

pdf Data sheet 11083813 3.22 MB
pdf Instruction 11083813 1.88 MB
pdf Modbus software manual 698.96 KB
lock 3D data - STEP / IGES
11083813
811.71 KB
zip Modbus Configuration Tool V1.20 746.87 KB
last update on Friday, 2. December 2016 - 8:08