Search form


MR-DOA4 Modbus RTU

The Modbus module with 4 digital outputs was developed for decentralized switching tasks. It is suitable for switching electrical components, such as motors, contactors, lamps, louvers, etc. With strong inductive loads, we recommend protecting the relay contacts additionally with an RC element. The outputs can be switched by means of standard registers via a Modbus master. Module address, bit rate and parity are set with two rotary switches on the front or by software.Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Protocol Modbus RTU
Address range 00 to 99
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage range 20 V to 28 V AC/DC (SELV)
Current consumption 200 mA (AC) / 70 mA (DC)
Relative duty cycle 100 %
Output / contacts 4 changeover contacts (4PST)
Output / switching voltage 250 V AC
Output / continuous current 5 A / output
Output / switching frequency 360 cycles/h
Display Green, red and yellow LED
Dimensions (W x H x D) 35 x 70 x 75 mm
Weight 95 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N110836132101
    Feature 14x OUT (relay CO)
    Feature 2


pdf Data sheet 110836132101 3.15 MB
pdf Instruction 110836132101 1.06 MB
pdf Modbus software manual 698.96 KB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
zip Modbus Configuration Tool V1.20 746.87 KB