The Modbus module with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 motorized fire dampers. With strong inductive loads, we recommend protecting the relay contacts with an RC element. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard registers via a Modbus master. Module address, bit rate and parity are set with two rotary switches on the front or by software.Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Protocol Modbus RTU
Address range 00 to 99
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 200 mA (AC) / 75 mA (DC)
Relative duty cycle 100 %
Inputs 4 x digital
Input / voltage 30 V DC
Input / high signal more than 8 V AC/DC
Output / contacts 2 changeover contacts (DPDT)
Output / switching voltage 250 V AC
Output / continuous current 16 A / output
Output / switch-on current 80 A (less than 20 ms)
Display Green, red and yellow LED
Dimensions (W x H x D) 50 x 70 x 75 mm
Weight 126 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N1108331326
    Colorgray
    Feature 14x IN (U or contact)
    Feature 22x OUT (relay CO)
    EAN-No4250184135623

Downloads

pdf Data sheet 1108331326 3.22 MB
pdf Modbus software manual 698.96 KB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
lock 3D data - STEP / IGES
1108331326
811.72 KB
zip Modbus Configuration Tool V1.20 746.87 KB
last update on Friday, 2. December 2016 - 8:08