KMAi-F8

The analog encoder is used for manual control variable settings for example for mixing valves, valve positions, temperature values etc. The module can be controlled in two operating modes that are set by means of the three level switch (ON, OFF, AUTO) on the front. The switch position is confirmed via the two external control contacts B1 and B2.

Switch position "ON"

The control variable can be set with the potentiometer on the front. The output signal 0 to 20 mA is available at contact Y. The current flow at input YR is not interrupted when the switch is in position ON or OFF.

Switch position "AUTO"

The input current (YR) is transmitted to the control variable output Y with a tolerance of ±5 % (full scale value).

  • Connection by spring clamp terminal blocks (push-in)
  • Setpoint generator
  • Manual control level with checkback function
  • LED brightness proportional to control variable
Input / operating voltage 24 V AC/DC
Input / power consumption AC 30 mA
Input / power consumption DC 19 mA
Input / voltage 0 V to 20 mA DC
Output / voltage 0 V to 20 mA DC
Display Red LED
Dimensions (W x H x D) 11.2 x 87.5 x 60 mm
Weight 43 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N110731
    Colorgray
    Feature 124 V AC/DC
    Feature 20 - 20 mA
    EAN-No4250184123231