Search form

Languages

KMA-F8

The analog encoder is used as encoder for manual control variable definition, e.g. mixing valves, valve positions, temperature values, etc. The module can be operated in three modes, which can be commuted by means of integrated three-level switches (ON, OFF, automatic). The switch position is signalized by external control contact terminals B1 and B2. The control variable can be set on the potentiometer at the front. The output signal 0 to 10 V is available on the Y terminal. If the switch is in "AUTO" position, the control variable is looped through over the YR terminal to the Y output without change.

  • Setpoint device
  • Manual control level with checkback
  • LED brightness proportional to control variable
Input / operating voltage 24 V AC/DC
Input / power consumption AC 30 mA
Input / power consumption DC 19 mA
Input / voltage 0 V to 10 V DC
Output / voltage 0 V to 10 V DC
Display Red LED
Dimensions (W x H x D) 11.2 x 87.5 x 60 mm
Weight 43 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N110730
    Colorgray
    EAN-No4250184123224

Downloads

pdf Data sheet 110730 221.61 KB
pdf Hinweis KRA-F 899144 155.89 KB
pdf Instruction 110730 1.37 MB
pdf Instruction 110730 1.27 MB
lock 3D data - STEP / IGES
110730
1.41 MB
last update on Saturday, 22. July 2017 - 2:48