Search form



CAN module with 4 digital inputs, which can be operated as contact or voltage inputs. It is suitable for detecting switch states, for example, of electrical limit switches on vent valves or auxiliary contacts of power contactors. The fieldbus module is an input module for universal use. It is controlled by means of the CAN bus. The module is addressed by means of an adjustable address, and the input states are transmitted in data bytes. If there is one (or more) relay output module(s) with the same address in the system, the respective outputs are switched.

Protocol CAN
Addressing range 00 to 99
Bus interface ©CiA standard 2.0B passive (two-wire bus)
Transmission rate 20 to 500 kBit/s
Operating voltage range 20 V to 28 V AC/DC (SELV)
Current consumption 63 mA (AC) / 21 mA (DC)
Relative duty cycle 100 %
Recovery time 550 ms
Inputs 4 x digital
Input / voltage 0 V to 10 V DC
Input / resolution 10 mV / (0 % to 100%)
Input / error approx. +/- 100 mV
Display Green, red and yellow LED
Dimensions (W x H x D) 35 x 70 x 65 mm
Weight 83 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N1105751319
    Feature 1
    Feature 2


pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
last update on Tuesday, 6. September 2016 - 4:30