Search form

Languages

S0/M converter 4 fold

4-channel impulse counter for counting impulses that are generated by energy counters via reed contacts or passive transistor outputs (open collectors) in proportion to the energy measured. Impulses of any potential-free contacts can be recorded for counting, for example, events up to a frequency of 15 Hz.The impulses generated by the energy counters are recorded by means of a standardized current interface to DIN EN 62053-31 class A. The 4-channel impulse counter occupies a clear M-Bus address specified by the manufacturer.Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Protocol M-Bus
Bus interface Two-wire bus
Transmission rate 300 Bit/s to 9600 Bit/s
Operating voltage 24 V AC/DC ± 10% (SELV)
Current consumption 50 mA DC
Inputs 4 x S0 to DIN EN 62053-31 Class A
Display green LED flashes at incoming pulse
Dimensions (W x H x D) 50 x 69.3 x 60 mm
Weight approx. 70 g
Operating temperature range -10 °C to +50 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N110556
    Colorgray
    EAN-No4250184122432

Downloads

lock ePLAN Daten 110556 279.46 KB
pdf Mounting instruction 110556 704.46 KB
lock 3D data - STEP / IGES
110556
667.4 KB
last update on Wednesday, 23. August 2017 - 3:22