LTRk-E12, 24 V AC/DC

Description

The fan timer relay was designed especially for controlling two-level motors. Response and switch-off delay can be adjusted separately and infinitely. A two-level switch is used for activation. The motor contactors are activated by two mutually blocking outputs. Mode of operation:

  • 1. If you directly select level 2, level 1 is first activated for the adjusted start-up time so that the fan can accelerate to nominal speed. Then level 2 is activated.
  • 2. When switching from level 2 back to level 1 or switching off, a switch-off delay is activated allowing the fan to run down before level 1 is activated.
  • 3. If level 1 has been activated for minimum the adjusted start-up time, it is immediately switched to level 2. When switching from level 1 to 2, the interruption may be max. 250 ms. If this time is exceeded, the procedure is as described under point 1.
Technical Data
General Data
24 V AC/DC
approx. 20 ms
Operating voltage
6 A AC1 / 1.5 A AC3
0 ms
approx. 30 ms
adjustable time of up to 30 s
adjustable time of up to 60 s
22.5 x 75 x 95 mm
150 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory
Part number
11028313
4250184121060
Downloads
  • 3D-Data - Registration required -
  • Data sheet
  • ePLAN data - Registration required -
× Do you have any questions?