LTRk-E12, 24 V AC/DC

The fan timer relay was designed especially for controlling two-level motors. Response and switch-off delay can be adjusted separately and infinitely. A two-level switch is used for activation. The motor contactors are activated by two mutually blocking outputs.Mode of operation:

  • 1. If you directly select level 2, level 1 is first activated for the adjusted start-up time so that the fan can accelerate to nominal speed. Then level 2 is activated.
  • 2. When switching from level 2 back to level 1 or switching off, a switch-off delay is activated allowing the fan to run down before level 1 is activated.
  • 3. If level 1 has been activated for minimum the adjusted start-up time, it is immediately switched to level 2. When switching from level 1 to 2, the interruption may be max. 250 ms. If this time is exceeded, the procedure is as described under point 1.
Operating voltage AC 230 V AC
Operating voltage (AC/DC) 24 V AC/DC
Recovery time approx. 20 ms
Output / voltage Operating voltage
Output / max. current 6 A AC1 / 1.5 A AC3
Response time for level 1 0 ms
Response time for level 2 approx. 30 ms
Start-up delay adjustable time of up to 30 s
Switch-off delay adjustable time of up to 60 s
Dimensions (W x H x D) 22.5 x 75 x 100 mm
Weight 150 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20