CPW-E12, 230 V AC, 1 - 10 A

The cosPhi monitor is used for detecting underload. The response value and the response time can be adjusted. It can also be used in combination with a frequency converter (frequency: 2 to 200 Hz). Monitoring is accomplished by recognizing the phase shift between current and voltage. This phase angle varies depending on the motor load.
The functions can be adjusted by means of bridges S1 - S2 - S3S1 - S2 open = relay deactivated with underloadS1 - S2 bridged = relay activated with underloadS1 - S3 open = with fault memoryS1 - S3 bridged = without fault memoryThe module can be unblocked remotely by means of a closing contact on S1 - S3.If there is a fault memory (no bridge over S1-S3), the fault message is active until it is acknowledged or the supply voltage is interrupted.

Operating voltage 230 V AC
Frequency range 2 to 200 Hz
Input / motor voltage 230 V AC / 400 V AC
Input / current min. 0.2 A / max. 10 A
Input / cosPhi response value 0 to 0.97, adjustable
Input / response time 1 to 100 s, adjustable
Output 1 changeover contact (SPDT)
Output / switching voltage max. 250 V AC
Output / continuous current max. 4 A
Output / switching frequency 1200 cycles/h
Display Green and red LED
Dimensions (W x H x D) 22.5 x 75 x 100 mm
Weight 170 g
Operating temperature range 0 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N1102810520
    Colorgray
    Feature 1measuring range
    Feature 21 - 10 A
    EAN-No4250184121039

Downloads

pdf Instruction 1102810520 691.07 KB
pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
last update on Thursday, 12. January 2017 - 3:30