Search form


EIW-C18, 230 V AC

Monitoring of direct or alternating currents in live systems. It is displayed whether the adjusted values are exceeded or not reached, and a switching process is triggered. The integrated 7-segment display indicates the sources of the fault. The current to be measured (AC or DC), an upper and a lower threshold value, a response delay and the fault memory (ON or OFF) can be adjusted manually on the device. The two current measuring ranges can be selected by means of the terminal blocks. Faults can be acknowledged directly on the device or by means of an external contact.
Variants:230 V AC or 24 V AC

Operating voltage 230 V AC, 50 Hz
Operating voltage 24 V AC
Current consumption max. 15 mA
Current measuring input B1 - B3 0.01 A to 1 A
Current measuring input B2 - B3 0.1 A to 15 A
Response delay 0.1 to 9.9 s, adjustable
Output 2 changeover contacts (DPDT)
Output / switching voltage max. 250 V AC/DC
Output / continuous current max. 8 A
Mechanical endurance 3 x 107 switching cycles
Electrical endurance 1 x 105 switching cycles
Display / error Two 7-segment displays
Display Green and red LED
Dimensions (W x H x D) 50 x 68 x 65 mm
Weight 200 g
Operating temperature range -5 °C to +55 °C
Storage temperature range -20 °C to +70 °C
Ingress protection for housing / terminal block IP40 / IP20

Technical Data 

  • P/N11027205
    Feature 1230 V AC
    Feature 2


pdf Produktuebersicht C|Logline 899905-05 EN 3.55 MB
lock 3D data - STEP / IGES
811.71 KB
last update on Tuesday, 11. October 2016 - 3:47